Programming
Remote Sync Enable: This feature controls the activation of notification appliances in such a way that all devices will turn on and
off at exactly the same time.
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2

Function Keys

The NFW-100X keypad has 4 programmable function keys. These keys can be programmed to allow rapid disable/enable of various fire
panel inputs and outputs during scheduled maintenance. pressing any function key results in a trouble signal at the panel. Pressing 1 on
System Setup Screen #1 displays the following:
FUNCTION KEYS
1=F1
3=F3
2=F2
4=F4
Function Keys Screen
To Enable or Disable the Function Key, press the 1 key while viewing the Function Keys Screen #1. Each press of the key will toggle the
screen between Key Enabled Yes and Key Enabled No.
Pressing 2 key while viewing the Function Keys Screen #1 allows the user to select individual zones that the Function Key will control.
Pressing 3 assigns all zones to the selected Function Key.
Each function key can be assigned to control any of the 4 onboard NAC circuits on the NFW-100X. By pressing the 2 key while viewing
the Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing 1, 2, 3, or 4 toggles the screen between Yes (controlled by function key) and No (not controlled by function key) for each
onboard NAC circuit.
F(X) KEY OPERATION
1=NACS
2=REM SYNC DISB
Function Keys Screen #2
SYSTEM SETUP
1=FUNCTION KEYS

2=BANNER

3=TIME-DATE
System Setup Screen #1
72
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be
displayed:
SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM
3=LANGUAGE
ENGLISH
System Setup Screen #4
1=F1
2=F2
Select 1, 2, 3, or 4 to program the corresponding Function Key. The following screens display for each
Function Key where "(X)" represents the number of the key chosen.
F(X) KEY OPERATION
1=KEY ENABLED
2=ZONES
3=ALL ZONES
Function Keys Screen #1
1=NAC 1
2=NAC 2 Y
The Remote Synchronization (TB8 on the FACP's main circuit board) can also be disabled through pro-
gramming of a function key. To disable remote synchronization, press the 3 key while viewing the Function
YES
Keys Screen #2. Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync
Disb No.
Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by
using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be
displayed:
1=FACTORY
2=USER DEFINED
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CHARGER ENAB
2=4XTM SPV ENAB
24HR
3=REM SYNC ENAB
System Setup Screen #5
FUNCTION KEYS
3=F3
4=F4
Function Keys Screen
F(X) KEY OPERATION
NO
1=NACS
2=REM SYNC DISB
Function Keys Screen #2
F(X) NACS
Y
3=NAC 3
N
4=NAC 4
N
Function Keys Screen
BANNER
Banner Screen
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Master Programming Level
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
3=MNS OVERRIDE
System Setup Screen #3
YES
NO
YES
NO
NO