PC Setup
Word(s)
DM 6608
DM 6609
DM 6610 to
DM 6614
Word(s)
Cycle Time Settings (DM 6615 to DM 6619)
The following settings are read by the CPU when program execution is started.
DM 6615
DM 6616
DM 6617
DM 6618
DM 6619
Downloaded from
Elcodis.com
electronic components distributor
Bit(s)
00 to 07
DeviceNet I/O Link Read
(IN) area settings
(CPM2B-S → Master)
08 to 15
00 to 15
00 to 15
Not used.
Note The startup operating mode will be as shown in the following table if bits 08 to
15 of DM 6600 are set to 00.
Connected
Programming Device
None
Programming Console
Other Device
Bit(s)
00 to 15
Not used.
00 to 07
Servicing time for RS-232C port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
08 to 15
RS-232C port servicing setting enable
00 (Hex): 5% of the cycle time
01 (Hex): Use time in bits 00 to 07.
00 to 07
Servicing time for peripheral port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
08 to 15
Peripheral port servicing setting enable
00 (Hex): 5% of the cycle time
01 (Hex): Use time in bits 00 to 07.
00 to 07
Cycle monitor time (Effective when bits 08 to 15 are set to 01, 02, or 03.)
00 to 99 (BCD): Setting (See bits 08 to 15, below.)
A fatal error will be generated and PC operation will stop if the cycle time exceeds the cycle mon-
itor time set here.
Cycle monitor enable (Setting in 00 to 07 × units; 99 s max.)
08 to 15
00 (Hex): 120 ms (setting in bits 00 to 07 disabled)
01 (Hex): Setting units: 10 ms
02 (Hex): Setting units: 100 ms
03 (Hex): Setting units: 1 s
00 to 15
Minimum cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Function
Data area
01 (Hex): I/O area 1 (IR 000 to IR 049)
02 (Hex): I/O area 2 (IR 200 to IR 227)
03 (Hex): DM area (DM 0000 to DM 2047)
04 (Hex): LR area (LR 00 to LR 15)
05 (Hex): HR area (HR 00 to HR 19)
06 (Hex): AR area (AR 00 to 23)
07 (Hex): Timer/counter area (TC 000 to TC 255)
Number of bytes
01 to 40 (Hex) (equivalent to 0 to 64 decimal)
Starting word address
0000 to 07FF (Hex) (equivalent to 0000 to 2047 decimal)
Not used.
Startup operating mode
DIP switch pin 4 ON
PROGRAM
Mode set on Programming Console mode switch
PROGRAM
Function
Section 4-6
DIP switch pin 4 OFF
RUN
75