Selecting an Installation Site

The CPM2B-S is resistant to harsh conditions and highly reliable, but install-
ing the PC in a favorable site will maximize its reliability and operating lifetime.
Be sure to install the CPM2B-S correctly, as outlined in this manual. Failure to
! C a u t i o n
do so may result in Board malfunction.

Installation Site Conditions

Note Do not install the CPM2B-S under any of the following conditions.
• Locations subject to direct sunlight.
• Locations subject to an ambient temperature below 0°C or over 55°C.
• Locations subject to an ambient humidity below 10% or over 90%.
• Locations subject to condensation as the result of severe changes in tem-
perature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to shock or vibration.
• Locations subject to exposure to water, oil, or chemicals.
Be sure that the conditions at the installation site conform to the CPM2B-S's
general specifications. Refer to 2-1-1 General Specifications for details.
Note Provide proper shielding when installing in the following locations:
• Locations subject to static electricity or other sources of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radiation.
• Locations near to power supply lines.

Panel/Cabinet Installation

Consider PC operation, maintenance, and surrounding conditions when
installing the CPM2B-S in a panel or cabinet.
The ambient operating temperature range for the CPM2B-S is 0°C to 55°C.
Be sure that there is adequate ventilation for cooling.
• Allow enough space for air circulation.
• Do not install the CPM2B-S above equipment that generates a large
amount of heat, such as heaters, transformers, or large resistors.
• Install a cooling fan or system when the ambient temperature exceeds
55°C.
Control panel
Fan
CPM2B-S
Air vent