1.4

Firmware update

Updating firmware
The firmware of an IM 151-3 PN HIGH FEATURE can be updated:
● Using a SIMATIC Micro Memory Card with at least 4 MB of memory.
● Via PROFINET IO, e.g., using HW Config or in the SIMATIC Manager via "Target system
Requirements
In order to update the firmware of an IM 151-3 PN HIGH FEATURE you require:
● SIMATIC Micro Memory Card (MMC) for the MMC update
● A PC or programming device with a facility for writing to a SIMATIC Micro Memory Card
NOTICE
When the firmware is updated, the stations in a line can fail.
Note
A firmware update with SIMATIC Micro Memory Card is not possible for interface modules
that were started with the "Prioritized startup" parameter. In this case you can delete the
parameter "Prioritized startup" by a "Reset to factory settings". Firmware updating with the
SIMATIC Micro Memory Card is subsequently possible again.
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)
Manual, 08/2010, A5E01584258-04
Additional information can be found on the Internet
(http://support.automation.siemens.com/WW/view/en/19241998/133100).
> Display accessible nodes".
For additional information, refer to the
STEP 7
, V5.3 or higher, SP 2
STEP 7
Online Help.
Properties
1.4 Firmware update