Maintenance

10.2 Firmware update

Result
Topological configuration:
1. The new I/O device automatically receives the device name with PROFINET IO via the IO
controller.
NOTE
New or factory setting
The I/O device only obtains the device names automatically with PROFINET IO with:
– New I/O device
– Set to factory settings
2. The new I/O device receives the connect telegram and startup data record from the IO
controller.
3. The new I/O device and all downstream I/O devices start up again by themselves.
No topological configuration:
1. The new I/O device must have the same name as the device name of the I/O device to be
replaced.
2. The new I/O device receives the connect telegram and startup data record from the IO
controller.
3. The new I/O device and all downstream I/O devices start up again by themselves.
Reference
You will find information on the device name in the STEP 7 online help or the MultiFieldbus
(https://support.industry.siemens.com/cs/ww/en/view/109773209) function manual.
10.2
Firmware update
Introduction
During operation, it may become necessary to update the firmware (e.g. for function
extensions).
Firmware updates are used to update the firmware of the I/O device.
NOTE
Temporary bus interruption
When you update the firmware of an ET 200eco PN M12‑L I/O device, then the MultiFieldbus
is briefly interrupted due to the reboot of the I/O device. This interruption generates an alarm
in the controller for all downstream MultiFieldbus devices.
88
Distributed I/O system ET 200eco PN M12-L
System Manual, 11/2023, A5E48753295-AG