Interrupt, error, and system messages
4.1 Diagnostics using LED display
Status and error displays
Table 4- 1
Status and error displays of the IM151-3
LEDs
SF
BF
MAINT
Off
Off
Off
*
*
*
*
Flashing
*
0.5 Hz
*
On
*
On
*
*
On
On
*
42
Meaning
ON
Off
There is no voltage at the interface
module, or the interface module has
a hardware defect.
On
There is voltage at the interface
module.
On
Faulty or no connect message frame
- no data transfer between the IO
controller and the interface module
(IO device), although the device is
physically connected to the switch.
Causes:
Incorrect device name
Configuration error
Parameter assignment error
The I/O controller is
disconnected/defective or the bus
cable to the controller is missing.
On
The IO device is not connected to a
switch.
On
The configured structure of the
ET 200S does not match the actual
structure of the ET 200S.
There is an error in an I/O
module, or the interface module
is defective.
Diagnostics data available
On
A brand new SIMATIC Micro
Memory Card is being formatted.
Interface module IM151-3 PN HIGH FEATURE (6ES7151-3BA23-0AB0)
Remedy
Switch on the 24 V DC supply
voltage at the interface module.
Check the interface module.
Check the configuration and
parameter assignment.
Check the device name.
Assign a valid device name to the
interface module.
Check the IO controller
Check to see if the rear panel bus
has been configured correctly (all
modules inserted, terminating
resistor installed)
Establish a connection to the IO
controller (via a switch).
Assign a valid device name to the
interface module.
Check the bus configuration.
Check that the bus connector is
correctly inserted.
Check whether the bus cable to
the
I/O controller is interrupted.
Check the ET 200S configuration
to see whether a module is
missing or defective, or whether a
non-configured module has been
installed.
Check the configuration (e.g. in
STEP 7
) and correct any
parameterization errors.
Replace the interface module, or
contact your Siemens
representative.
Remove error, e.g. wire break
Wait until the formatting sequence
is complete. This may take several
minutes. If the LED behavior
changes, the formatting process is
complete.