Maintenance

6.2 Online firmware update by means of STEP 7 Manager

6.2
Online firmware update by means of STEP 7 Manager
Introduction
To update the firmware of the ET 200eco PN including its I/O devices, you require the *.UPD
files containing the current firmware version.
Requirements
● An online firmware update can be performed in
● The I/O device of the station whose firmware is to be updated must be accessible online.
● The files containing the current firmware versions must be available in the file system of
Performing a firmware update
1. Start
2. In the SIMATIC Manager select PLC > Available stations.
3. Select the I/O device.
4. Select the menu command PLC > Update Firmware. I/O devices without NameOfStation
5. In the Update Firmware dialog, select the path to the firmware update files (*.UPD) using
6. After you have selected a file, the information in the bottom boxes of the "Update
7. Click "Run". The I/O device then automatically updates the firmware.
72
The network card used must be set to "TCP/IP (Auto)" in the SIMATIC Manager under
Options > Set PG/PC Interface.
your programming device or PC. A folder must contain the files of one firmware version
only.
NOTICE
The I/O device must be reset to the factory setting before the firmware update is carried
out when special port parameter assignments have been carried out.
STEP 7
.
(NoS) are displayed with their MAC address.
STEP 7
In
V5.4 SP5 or higher, Slot 0 must also be specified for the I/O devices. In
STEP 7
previous versions of
When setting the ET 200eco PN IO-Link Master, you can carry out updating of functional
units:
– Slot 0: ProfiNet functional unit
– Slot 1: IO-Link functional unit
– Slot 2: 8 DI + 4 DO functional unit
the "Browse" button.
Firmware" dialog box indicate the I/O device for which the file is suitable and from which
firmware version.
If the firmware is to be loaded directly after the installation, select the "Activate firmware
after loading" check box here. If the check box is not selected, the firmware becomes
active after the next Power Off/On.
STEP 7
this setting is specified implicitly.
Operating Instructions, 06/2009, A5E01250250-04
V5.4 + SP2 or higher.
ET 200eco PN