Samsung AC BNPDBC Series User & Installation Manual page 57

Table of Contents

Advertisement

Fixing the power cable
CAUTION
• Do not let the power cable come into contact with the
pipes inside the outdoor unit. If the power supply cable
touches the pipes, the vibration of the compressor is
transferred to the pipes and can damage the power
supply cables or pipes, creating the danger of fire or
explosion.
• Make sure that the place where the sheath of power
supply cable is removed is inside the power supply box.
If it is impossible, you should connect the protection
tube for power cable to the power supply box.
• After arranging the power cable into the power supply
box, tighten the cover.
Connect the ring terminal
1 Cut the power cable to an appropriate length and connect it
with the solderless terminal.
2 After connecting the power cable to the terminal as seen in the
illustration, fix it with cable tie.
3 Fix the housing, which has an insulator to the terminal board.
3 phase 4
wires
(380-415 V~)
ELCB
Or
MCCB+
ELB
Sub unit communication cable
L1(R)
L2(S)
L3(T)
L4(N)
L1(R)
L2(S)
L3(T)
L4(N)