Deciding on where to install the product
Sea breeze
Sea
• If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to
block the sea breeze.
Protection wall
Sea breeze
Sea
• Install the outdoor unit in a place where water can drain smoothly.
If you cannot find a place satisfying above conditions, please contact manufacturer. Make sure to
clean the sea water and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor
on heat exchanger. (At least one time per one year.)
• Choose a place where there is no direct sunlight.
• Choose a place where it could not come into contact with snow and rain.
• Choose a place where flammable gas does not leak.
• Choose a place where the indoor and outdoor unit can be connected with a pipe.
• Choose a place where there is no direct sunlight.
• Choose a place where it could not come into contact with snow and rain.
• Choose a place where flammable gas does not leak.
• Choose a place where the indoor and outdoor unit can be connected with a pipe.
WARNING
• After installing the outdoor unit, apply rust inhibitor on the internal pipes and heat exchanger.
If you don't apply rust inhibitor, airborne corrosive gas (such as sulfur compounds, hydrogen sulfide
and ammonia) and salty dust may cause pipe corrosion which will lead to refrigerant leakage.
Inspect the outdoor unit at least once a year and re-apply the rust inhibitor where it is damaged
(worn out).
• When applying the rust inhibitor, please be aware of the following:
Turn off the power before spraying the rust inhibitor.
Wear protective goggles and mask before spraying.
Clean the dusty surface with clean fabric or paper before spraying.
Make sure that wind is blowing from worker's back when spraying.
Do not spray on the PCB panel and electric parts.
32 English
Outdoor unit
• Protection wall should be constructed with a solid material
such as concrete to block the sea breeze and the height and
Outdoor
the width of the wall should be 1.5 times larger than the size
unit
of the outdoor unit. Also, secure over 700mm between the
protection wall and the outdoor unit for exhausted air to
ventilate.
Outdoor unit
Sea breeze
Sea