Wiring work
Connecting power and communication cable
This product uses the power for 380 V 60 Hz, 3-phase 4 wires. The indoor unit uses the power for 220 V 60
Hz, single-phase. The power cables for both units must be separated.
1 Remove the cover of the electrical component on the outdoor unit.
2 Connect the power cable (R, S, T, N) to the R, S, T, N of the terminal on the electrical component on the
outdoor unit. (Power cable must be purchased separately.)
3 When tightening the screw on the terminal block, apply appropriate tightening torque to assemble
cables to the terminal.
4 Install ELB [Earth Leakage breaker (for 4 wires)] for air conditioner. It must be selected according to the
starting current of the compressor.
Indoor unit
1(L) 2(N)
Model
Outdoor unit
Indoor unit
AC078BXPDHC AC078BNPDBC
AC096BXPDHC AC096BNPDBC
54 English
Outdoor unit
Communication
terminal
F1
F2
F2
F1
R
S
Indoor-to-outdoor
unit connection wire
Power supply cable for outdoor unit
Power supply cable for indoor unit
Outdoor unit
Rated
Hz
Volts Min. Max.
60
380
60
380
Distributing board
Earth
Earth
T
N
Input Current (A)
Voltage
Outdoor
Range
(Down_Amp) Indoor
Cooling
342
418
25.0
342
418
25.0
ELB for
ELB for
outdoor unit
indoor unit
Earth
R
S
T
N
L
N
Power supply
Indoor
MCA MFA MCA MFA
2.5
2.5
3.1
4.5
4.5
5.6
Outdoor
25.0 31.3
25.0 31.3