Samsung AC BNPDBC Series User & Installation Manual page 69

Table of Contents

Advertisement

Error
No.
Code
Operation temperature protection of the top of the
47
E463
compressor
48
E464
IPM Over Current(O.C)
49
E465
Comp. Over load error
50
E466
DC-Link voltage under/over error
Error due to abnormal rotation of the compressor or
51
E467
unconnected wire of compressor
52
E468
Error on current sensor (Short or Open)
53
E469
Error on DC-Link voltage sensor (Short or Open)
Outdoor EEPROM checksum error between MAIN
54
E471
and INVERTER
55
E472
AC Line Zero Cross Signal out
56
E473
Comp Lock error
Error on IPM Heat Sink sensor of inverter 1 (Short or
57
E474
Open)
58
E475
Error on inverter fan 2
59
E478
Error due to overcurrent of Fan1
60
E484
PFC Overload (Over current) Error
Error on input current sensor of inverter 1 (Short or
61
E485
Open)
62
E486
Over-voltage/low-voltage error of Fan1
63
E487
Hall IC connection error of Fan1
64
E489
V-limit error on Fan1 of compressor
65
E491
Error due to DataFlash of Fan1
66
E493
Output current sensor error of Fan1
67
E496
DC voltage sensor error of Fan1
68
E499
Heat sink temperature sensor error of Fan1
69
E500
IPM over heat error on inverter 1
70
E508
Smart install is not installed
Meaning
Remarks
1. Check if the service valve is open
2. Check for refrigerant leakage (pipe
connection, pipe extension and others)
and charge refrigerant if necessary
3. Check the location of the outdoor unit
and change the location if necessary
4. Re-install the outdoor unit if necessary
IPM
-
Check AC Power and DC Link Voltage
Check Comp wire
Check Outdoor Inverter PBA.
-
Check Outdoor EEPROM PBA
-
-
heck Outdoor Inverter PBA
Fan2 error
Fan1 error
Check Outdoor Inverter PBA.
Check Outdoor EEPROM PBA
Fan1 error
Fan1 error
Fan1 error
Fan1 error
Fan1 error
Fan1 error
Fan1 error
Check Outdoor Inverter PBA.
-
English
69