Samsung AC BNPDBC Series User & Installation Manual page 53

Table of Contents

Advertisement

NOTE
• Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66 / CENELEC
H07RN-F)
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than
or equal to Ssc (*2) at the interface point between the user's supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected only to a supply with a short-circuit
power Ssc greater than or equal to Ssc(*2). [Ssc (*2)]
AC078B*PD*C
AC096B*PD*C
Power wiring diagram
Connect the power cable of the outdoor unit after checking that R-S-T-N (3-phase 4 wires) is properly
connected. If the power of 380 V is supplied to the N phase, PCB and other electrical parts will be damaged.
NOTE
• Before supplying power to the outdoor unit, be
sure to check the voltage of the distribution board.
The voltage between phases for the 3 phase 4
wires 380 V is as follows:
R phase and S phase: 380 V
R phase and T phase: 380 V
S phase and T phase: 380 V
R phase and N phase: 220 V
S phase and N phase: 220 V
T phase and N phase: 220 V
• Communication cables between the indoor and
outdoor units do not have polarity.
CAUTION
• Arrange the cables with a cable tie. ELCB and ELB must be installed because there is risk of electric
shock or fire.
MODEL
Ssc[MVA]
3.57
5.08
3 phase 4
wires
380 V
MCCB+
ELB
Outdoor
Or
Unit
ELCB
Earth
Communication cabale
(outdoor-to-indoor unit)
Single phase
220 V
MCCB+
ELB
Or
Indoor
ELCB
Unit
Earth
English
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac bxpdhc series

Table of Contents