Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 942

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

¢ Auxiliary heater output (External output 4)
When indoor unit fan and compressor is turned on in heating operation, the signal is output from
connector.
NOTE: Corresponding indoor units: All duct type
Specifications of the signal output performance are as shown as follows:
Example: When set temperature (Ts) is set at 22 °C;
And room temperature (Tr) increase above
12 °C, signal output is on.
And Tr increase above 21 °C, signal output is
off.
And Tr decrease below 19 °C, signal output is
on.
And Tr decrease below 10 °C, signal output is
off.
The output also turns off on defrost operation and oil recovery operation.
• Fan delay switch (Indoor unit)
This is used to continue the indoor unit fan operation for 1 minute after thermo off in heating mode.
1 minute delay control setting by DIP switch (2-3) on the PCB is "On".
Heating
operation
Indoor unit fan
CNB01 (1-5)
output
CAUTION
• Install an auxiliary heater between the indoor unit and the outlet.
• Be sure to use delay control of the fan.
• To avoid a fire caused by self heat of the auxiliary, design and install the auxiliary properly with
considering protection by auxiliary itself.
Our company is not responsible for the system designed including auxiliary with improper instal-
lation.
3-2. External output
Operation
Stop
On
Off
12 V
0 V
External
heater
Supply air
- (08-24) -
OFF
Tr-Ts = -1 °C
ON
Tr-Ts = -10 °C
OFF
1 min
Indoor
unit
Return air
Tr-Ts
Tr-Ts = -3 °C
Tr-Ts = -12 °C
3. Indoor unit