Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 491

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

¢ Specifications
Power source voltage
Power source frequency
Input power
Display
LED indicator
External interface
Usage temperature range
Usage humidity range
Storage temperature range
Storage humidity range
Dimensions
(H × W × D)
Weight
Fuse capacity
 Wiring specifications
Use
Power supply cable
(for stranded wire)
Power supply cable
(for solid wire)
Transmission cable
External input/output
cable
LAN cable
2-4. Central remote controller (UTY-DCGZ)
V
Hz
W
°C
%
°C
%
mm
g
A
Cable size
2
0.8—1.25 mm
60245 IEC 57 or equivalent
(18—16 AWG)
2
0.8—2.0 mm
(18—14 AWG)
LEVEL4 (NEMA) non-polar 2-
2
0.33 mm
core, twisted pair solid core
diameter 0.65 mm, shielded
(22 AWG)
2
0.33 mm
Polar 2-core, twisted pair
Max cable length: 25 m
(22 AWG)
Category 5 or more straight
- (05-45) -
1 Ø AC 100—240
7.0-inch TFT color LCD panel (WVGA)
Power LED (Green)
Transmission line
External input: Either emergency stop, batch
operation/stop, electricity meter
(Either Dry contact or apply voltage can be selected.)
External output: Operation state, error state
Wired LAN (100 BASE-TX)
0 to 40
0 to 85 (no condensation)
-20 to 70
0 to 85 (no condensation)
134.6 × 216.2 × 37.9
Wire type
1 Ø AC 100—240 V 50/60 Hz,
1 Ø AC 100—240 V 50/60 Hz,
LonWorks compatible cable
type
Use cable in accordance with
cable
50/60
7
800
5
Remarks
2-wire + ground
(Always ground the unit)
2-wire + ground
(Always ground the unit)
local rules for cable.
100 BASE-TX support