5.
Send the information by pressing the START/STOP button once. A beeping sound (2 short
beeps, 1 long beep, 2 short beeps, and 1 long beep) will be emitted if the command is accept-
ed.
In the following cases, the setting signal will not be accepted correctly and 5 short beeps will be
emitted:
• The indoor unit address number is set out of range (64 or more)
• The setting of the rotary switch on the indoor unit PCB is not set to "00"
6.
Indoor unit lamps will indicate the indoor unit address data number as follows:
OPERATION
(Green)
Lit continuously
When the address setting is "0", TIMER lamp and FILTER lamp will not flash.
 Confirmation of address setting
To confirm the address setting is properly configured, press the TIMER set (+) button.
TIMER set (+) button
1-4. Address setting by remote controller
TIMER
FILTER
(Orange)
(Red)
Flashes times of
Flashes times of
address numbers
address numbers
(the left digit)
(the right digit)
Beeps are emitted
intermittently
(2 short beeps,
1 long beep, 2 short beeps,
and 1 long beep)
Example) ADDRESS: 34
OPERATION lamp
(Green)
TIMER lamp
(Orange)
3 times
0.5sec ON / 0.5sec OFF
FILTER lamp
(Red)
Beeps are emitted intermittently as follows:
Correct:
Wrong:
(3 sec)
- (07-21) -
0.5 sec ON / 0.5 sec OFF
1 to 10 sec
4 times
1 to 10 sec
(2 short beeps,
1 long beep, 4 short beeps,
and 1 long beep)
(2 short beeps and 1 long beep)
1. System settings

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-ivs aj 054lcldh seriesAirstage j-ivs aj 045lcldh seriesAirstage j-ivs auxb004glehAirstage j-ivs auxb007glehAirstage j-ivs auxb009glehAirstage j-ivs auxb012gleh ... Show all

Table of Contents