Units other than [A] and [B] must not be connected to an electricity meter together with other
indoor units. If connected, the electricity amount of DDC, damper and heater is also charged to
the other indoor units.
¢ Electricity meter system
Electricity meter system is the connection configuration of 1 electricity meter and the air conditioner
units which are connected to the power line under it. This is set on the System controller.
Set the System controller to match the actual electricity meter installation configuration.
Since the electricity charge apportionment function and energy saving function perform the control
using the power consumption data from an electricity meter, it is necessary to set an electricity meter
system on the System controller.
When installing electricity meters as shown below, 5 electricity meters systems are set as follows.
Electricity meter system 1
Whm
2-30. Electricity charge apportionment setting (System controller, Touch panel
controller)
DX kit
[B] External fan
[A] Run/stop state
External output linked units
DDC/Damper/Heater, etc.
Electricity meter system 2
Whm
Whm
Whm
Whm
Electricity meter system 4
Electricity meter
- (07-166) -
Whm
The electricity meter is installed so that the
units other than [A], [B] and indoor units
are included.
Electricity meter system 3
Whm
Electricity meter system 5
2. Function settings