Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 799

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

 Refrigerant circuit address setting
NOTE: Perform this setting on the master remote controller.
1.
By pressing the + or - button, select a remote controller address. (Select the indoor unit you
want to operate.) Then press the ENTER button.
2.
By pressing the + or - button, display function number "02". Then press the ENTER button.
3.
By pressing the + or - button, set up the refrigerant circuit address. (The setting range is from
"00" to "99".)
• When the address data is properly set up on the indoor unit, the set number will be dis-
played. (GOOD)
• When the address data is not set up correctly, "- -" is displayed. (ERROR) Back to the previ-
ous step and set up the indoor unit address data again.
4.
To return to the address selection screen, press the ENTER button. If setting has been com-
pleted, press MENU button to return to the Menu 2 item selection screen.
 Completion of setting mode
To exit the setting mode and return to the regular display, hold down the 3 buttons of MENU, <, and
ENTER at the same time for 2 seconds or longer.
1-4. Address setting by remote controller
Example: When setting at all the indoor units
Example: When refrigerant circuit address data "18" is set up
ERROR
- (07-53) -
Remote controller address
Function number
Refrigerant circuit address
GOOD
1. System settings