Fujitsu Airstage J-IVS AJ 040LCLDH Series Design & Technical Manual page 623

Hide thumbs Also See for Airstage J-IVS AJ 040LCLDH Series:
Table of Contents

Advertisement

• Type: Gateway
BACnet
object
Code (II)
type
Device
Device information
00
Lon network adapter error status
BI
01
Gateway status error
02
ES status
BO
02
ES setting
00
Lon network adapter error code
01
Gateway error code
MI
02
ECA* status
MO
01
ECA* setting
Notification
00—99 Notification class
00
Calendar "Holiday-1"
CAL
01
Calendar "Holiday-2"
02—32 Calendar "Special day-1"—"Special day-30"
Schedule
00—99 Schedule timer
*: Electricity charge apportionment
NOTES:
• To protect the compressor of the outdoor unit, carefully read and understand the following cau-
tions that may affect the operation of compressor before executing the setting.
CAUTION
• When regularly making the following settings to the same outdoor unit by using schedule
function etc., leave the following interval.
<Corresponding function>
• Reset outdoor unit forced off mode
• When performing periodical settings like schedule settings for the following functions, per-
form the setting to all indoor units in the same refrigerant system simultaneously, conforming
to the timing restriction described below.
<Corresponding function>
• Start operation
• Release indoor unit forced thermostat off mode
• Forced thermostat off instruction, outdoor unit forced off instruction, and capacity saving setting
– Only one equipment can send these instructions for each refrigerant system.
– When these instructions are sent by multiple equipment (eg. from System controller and BAC-
net gateway at the same time), the system may not respond as instructed or may cause mal-
function.
• The electricity charge apportionment function of VRF system can only be performed from one
equipment simultaneously. Therefore, ECA setting, required to be set before performing elec-
tricity charge apportionment, can only be sent from one equipment simultaneously.
• The energy saving function of VRF system can only be performed from one equipment simulta-
neously. Therefore, ES setting, required to be set before performing energy saving, can only be
sent from one equipment simultaneously.
3-10. BACnet gateway (Software: UTY-ABGXZ1)
Function name
Inactive
Text-1
Normal
Normal
Not used
Not used
Invalid
Stop
More than 10 minutes
More than 10 minutes
- (05-177) -
Unit
Active
Text-2
Text-3
Abnormal
Abnormal
Energy saving
Energy saving
Refer to FGL original error code
Refer to FGL original error code
Invalid
Include indoor
(Stop)
unit only
Include indoor
Exclude indoor
unit only
and RB unit
More than 6 minutes
must elapse
• Set outdoor unit forced off mode
More than 3 minutes
must elapse
must elapse
• Stop operation
• Set indoor unit forced thermostat off mode
must elapse
Text-4
Text-5
Text-6
Exclude indoor
Include indoor
Include RB unit
and RB unit
and RB unit
Include indoor
Include RB unit
and RB unit
3. Adaptor/Convertor units