¢ Installation
• When connecting to the connector
– For non-polar 2 wire
1. Use a tool to cut off the terminal on the end of the remote controller cable, and then re-
move the insulation from the cut end of the cable as shown below.
2. Connect the remote controller cable and connecting cable as shown below. Be sure to in-
sulate the connection between the cables.
3. Connect the remote controller cable to the connecting cable, and insert it to the connector.
Set the DIP switch (SW1) to "2WIRE" on the PCB of the indoor unit.
NOTE: Layout of terminal block and PCB is varies depending on the type of indoor
3-13. External switch controller (UTY-TERX)
Insulated
connection
Remote
controller cable
(Non-polar)
Set the DIP switch
(SW1) to "2WIRE"
Connect to earth
Functional grounding
(ground) screw
(If necessary)
Remote controller
cable (Non-polar)
unit.
- (05-194) -
20 mm
Remote
controller cable
(Non-polar)
White
Connecting
cable
Red
Black
Cut and
insulate
Indoor unit
PCB
Connector CNC01
Connecting cable
(onboard)
SW1
Connector
(adapter)
Indoor unit
PCB
3. Adaptor/Convertor units