Figure 25: D8129 Connections to the D7412GV3

1 - D8129 OctoRelays for relay numbers 1 to 64.
Connect OctoRelays in parallel.

10.1.1 Configuring the D8129 OctoRelay

Five switches on the OctoRelay determine the relay
numbers for the eight relay outputs (Table 17).
Table 17:
D8129 OctoRelay Switch Settings
Panel
D8129 OctoRelay
Relay
Switch Setting
Number
1 to 8
Off-On-On-On-On
9 to 16
On-Off-On-On-On
17 to 24
Off-Off-On-On-On
25 to 32
On-On-Off-On-On
33 to 40
Off-On-Off-On-On
41 to 48
On-Off-Off-On-On
49 to 56
Off-Off-Off-On-On
57 to 64
On-On-On-Off-On
D7412G Maximum
65 to 72
Off-On-On-On-On
73 to 80
On-Off-On-On-On
81 to 88
Off-Off-On-On-On
89 to 96
On-On-Off-On-On
97 to 104
Off-On-Off-On-On
105 to 112
On-Off-Off-On-On
113 to 120
Off-Off-Off-On-On
121 to 128
On-On-On-Off-On
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
D9412GV3/D7412GV3 | Operation and Installation Guide | 10.0 Off-Board Relays
On Panel, Connect
D8129 to:
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 1 Terminal 28
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
Zonex 2 Terminal 26
2 - Power limited

10.1.2 Relay Outputs

Relay outputs can activate when you are
setting the OctoRelay switches or
programming the control panel.
Disconnect equipment connected to relay
outputs when you perform these
functions.
Each OctoRelay output provides a Form C dry contact
rated for 1.0 A at 12.0 VDC. Normally-open, common,
and normally-closed terminals are available for each
relay output. When an individual output is activated,
continuity exists between the normally-open and
common terminals. When the output is not activated,
continuity exists between the normally-closed and
common terminals.

10.1.3 Installation

Set the switches on the OctoRelay before installing it
in the enclosure. Refer to Section 10.1.1 Configuring
the D8129 OctoRelay.
Install the OctoRelay in the enclosure with the control
panel (Figure 2 on page 9) or in an adjacent
enclosure that is no more than 1.5 m (5 ft.) from the
control panel. Use 1.5 mm (16 AWG) to 0.8 mm
(22 AWG) wire.
To install OctoRelays in the enclosure with the control
panel:
51