Figure 20: Connecting D8128D OctoPOPITs to the D9412GV3
1 - Zonex Bus 1, Switch 1 ON (Points 9 to 72)
2 - Bus 1
3 - First address on Zonex Bus 1
4 - Last address on Zonex Bus 1
5 - Zonex Bus 1, Switch 1 OFF (Points 73 to 127)
6 - Sensor loops
Refer to Address Switches in Section 9.4.4 Setting the OctoPOPIT Switches on page 44 for
information about making these switch settings. Refer to Table 15 on page 44 for information
about setting Switch 5.
For system supervision, do not use looped wire terminals. Break the wire run to provide
supervision of the connections.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
D9412GV3/D7412GV3 | Operation and Installation Guide | 9.0
7 - Zonex Bus 2, Switch 1 ON (Points 129 to
192)
8 - Bus 2
9 - First address on Zonex Bus 2
10 - Last address on Zonex Bus 2
11 - Zonex Bus 2, Switch 1 OFF (Points 193 to
240)
Off-Board Points
46