Figure 36: D9412Gv3, Input Points And Peripheral Devices System Wiring - Bosch D9412GV3 Operation And Installation Manual

Hide thumbs Also See for D9412GV3:
Table of Contents

Advertisement

D9412GV3/D7412GV3 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
.

Figure 36: D9412GV3, Input Points and Peripheral Devices System Wiring

1 - (Optional): For 24 V applications use a UL 1481
listed, regulated, power-limited 24 VDC power
supply with a D130 Relay Module. Refer to the
D130 Installation Instructions (P/N: F01U072455)
for correct wiring requirements.
2 - D130 Relay Module
3 - D125B Powered Loop Interface Module
4 - To UL Listed two-wire smoke detectors. Refer to
Two-Wire Smoke Detectors in the
D9412GV3/D7412GV3 Approved Applications
Compliance Guide (P/N: F01U143069) for a
listing of compatible two-wire smoke detectors.
Use zero retard except for waterflow devices.
All external connections except Terminal 5 (battery positive) are power limited.
Bosch Security Systems, Inc. | 10/10 | F01U143070-03
5 - P105BL1 1 kW resistor (P/N: F01U033966):
For typical burglar alarm applications.
6 - D129 Dual Class A Initiation Circuit Module:
Provides optional Waterflow Alarm Retard
feature. Not suitable for two-wire smoke
detectors.
67

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv3

Table of Contents