10.0 Off-Board Relays

10.1

D8129 OctoRelay

Use the D8129 OctoRelay to add relay outputs to the
system in groups of eight. The D7212GV3 allows up
to 24 relay outputs. Review Section 6.0 Power
Outputs on page 24 to ensure that enough power is
provided for the OctoRelays and other powered
devices that are connected to the system.
OctoRelays for relay numbers 1 to 24 connect to
Zonex 1, Terminal 28. Refer to Figure 19 on this
page.
Alarm output, auxiliary relay, sensor reset, arming
status, point status, alarm memory, or remote
functions can be assigned to the OctoRelay outputs
individually. Refer to Relay Parameters in the
D7212GV3 Program Entry Guide (P/N: F01U170808)
for programming details.

Figure 19: D8129 Connections to the D7212GV3

1 - D8129 OctoRelays for relay numbers 1 to 24.
Connect OctoRelays in parallel.
Bosch Security Systems, Inc. | 10/10 | F01U143079-03
D7212GV3 | Operation and Installation Guide | 10.0
D8129 Restricted for Fire Systems: D8129 relay
outputs are not supervised and cannot be used in fire
or combined fire and burglary installations for primary
indicating devices.

10.1.1 Configuring the D8129 OctoRelay

Five switches on the OctoRelay determine the relay
numbers for the eight relay outputs (Table 16).
Table 16:
Panel Relay
Number
1 to 8
9 to 16
17 to 24
2 - Power limited

D8129 OctoRelay Switch Settings

D8129 OctoRelay
On Panel, Connect
Switch Setting
D8129 to:
Off-On-On-On-On
Zonex 1 Terminal 28
On-Off-On-On-On
Zonex 1 Terminal 28
Off-Off-On-On-On
Zonex 1 Terminal 28
Off-Board Relays
43