Input; Input Options; Totalizers - Siemens SITRANS F Operating Instructions Manual

Coriolis flowmeters with hart
Hide thumbs Also See for SITRANS F:
Table of Contents

Advertisement

Functions

8.7 Totalizers

8.6.6

Input

If the input is activated with a logic signal (15 - 30 V DC), the meter carries out an activity
selected in the menu.
8.6.6.1

Input options

The following input options are available:
● Start dosing
● Hold / continue dosing
● Stop dosing
● Zero adjust
● Reset totalizer
● Resets all totalizers simultaneously
8.7
Totalizers
Totalizer functions
SITRANS FC430 has three independent totalizers that can be used for the summation of
massflow, volumeflow, corrected volumeflow, fraction A (volumeflow or massflow) or fraction
B (volumeflow or massflow).
The totalizers can be configured to count balance (net flow), positive flow or negative flow.
In case of failure in the system, the totalizer fail safe mode can be set to:
- Hold: the totalizer holds the last value before the failure occurred
- Run: the totalizer continues counting the actual measured value
- Memory: the totalizer continues counting based on the last input value (for example
massflow) before the failure occurred.
The totalizers can be operated via the Local User Interface or HART (for example SIMATIC
PDM). The totalizers can be reset or preset.
128
– When this function is activated, it will pause the dosing. When it is deactivated, the
dosing will continue
– Sets the digital output to "Off" and resets the dosing counter
– Starts the automatic zero point adjustment. This function employs the existing
configurations and presumes that the process conditions are prepared for the zero
point adjustment routine
– Resets one of the internal totalizers 1, 2 or 3 (depending on configuration)
SITRANS FC430 with HART
Operating Instructions, 03/2012, A5E03361511-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fc430

Table of Contents