Transmitter
SITRANS FC
Fig. 97: Passive status output connection P/Sout or Sout for solenoid valve circuit
A relay must be connected in series to switch alternating voltage.
Passive pulse or
Output signals according to EN 60947-5-6 (previously NAMUR, worksheet NA001):
status output P/Sout
(NAMUR)
SITRANS FC
1
Fig. 98: Passive pulse or status output with switching amplifier connected in series

13.4.1.4 Input signals

Active current input
An individual analog power input is available for external analog devices.
lin
The active current input lin is provided for connecting a two-wire transmitter with an
output signal of 4 – 20 mA.
Nominal input current range
Maximum input current range
Internal power supply
Internal load resistance SITRANS FC
SITRANS FC
24 V
0 V
Fig. 99: Connection of external device with passive current output
Passive current
The passive current input lin is provided for connecting a four-wire transmitter with an
input lin
output signal of 4 – 20 mA.
P/Sout+ or Sout+
P/Sout- or Sout-
Relay
Solenoid valve
Magnetic valve power supply
Protective diode
1kΩ
P/Sout+
10kΩ
P/Sout-
Passive pulse or status output
Switching amplifier
Iin+
Iin-
External passive current output device
1
4
3
2
Value
4 – 20 mA
2.4 – 21.6 mA
24 V
±20 %
DC
≤ 160 Ω
1
A5E52748375-AA, 2023/09
FC6x0
Wiring
2
133 / 194