Hitachi SH1 Series Basic Manual page 70

Hide thumbs Also See for SH1 Series:
Table of Contents

Advertisement

Chapter 4
[bA-70] to [bA-71][bA201] to [bA249]
Cooling-fan operation
Code/Name
bA-70
00(Always ON)/
Cooling fan
01(While inverter operates)/
control method
02(Depends on temperature)
selection
bA-71
Clear
00(Disable)/01(Clear)
accumulated cooling fan
run time monitor
・The Inverter cooling fan can be stopped.
・If you change the cooling-fan, assigning [bA-71]=01 you
will be able to clear the accumulated operation time.
2nd motor When Intelligent Input terminal 024[SET] is enabled.
Code/Name
bA201 Upper frequency limit source selection,
2nd-motor
bA202 Upper Frequency limit, 2nd-motor
bA203 Lower Frequency limit , 2nd-motor
bA210 Torque limit selection, 2nd-motor
bA211 Torque limiting parameters mode selection,
2nd-motor
bA212 Torque limit 1 (Forward drive), 2nd-motor
bA213 Torque limit 2 (Reverse regenerative),
2nd-motor
bA214 Torque limit 3 (Reverse drive), 2nd-motor
bA215 Torque limit 4 (Forward regenerative),
2nd-motor
bA216 Torque limit LADSTOP selection, 2nd-motor Same as bA116
bA220 Overcurrent suppression enable,
2nd-motor
bA221 Overcurrent suppression level, 2nd-motor
bA222 Overload restriction 1 mode selection,
2nd-motor
bA223 Overload restriction 1 active level,
2nd-motor
bA224 Overload restriction 1 action time,
2nd-motor
bA226 Overload restriction 2 mode selection,
2nd-motor
bA227 Overload restriction 2 active level,
2nd-motor
bA228 Overload restriction 2 action time,
2nd-motor
bA240 Overvoltage suppression enable,
2nd-motor
bA241 Overvoltage suppression active level,
2nd-motor
bA242 Overvoltage suppression active time,
2nd-motor
bA244 Constant DC bus voltage control P gain,
2nd-motor
bA245 Constant DC bus voltage control I gain,
2nd-motor
bA246 Over magnetization function selection,
2nd_motor
bA247 Over magnetization function output filter
time constant, 2nd-motor
bA248 Over magnetization function voltage gain,
2nd-motor
bA249 Over magnetization function level setting,
2nd-motor
Initial
Range (unit)
value
00
00
Range
Initial
(unit)
value
Same as bA101
Same as bA102
Same as bA103
Same as bA110
Same as bA111
Same as bA112
Same as bA113
Same as bA114
Same as bA115
Same as bA120
Same as bA121
Same as bA122
Same as bA123
Same as bA124
Same as bA126
Same as bA127
Same as bA128
Same as bA140
Same as bA141
Same as bA142
Same as bA144
Same as bA145
Same as bA146
Same as bA147
Same as bA148
Same as bA149
For parameter configuration
Reduction of electromagnetic sound
Code/Name
bb101
Carrier
frequency setting,
1st-motor
bb102
Sprinkle
carrier pattern
selection, 1st-motor
bb103
Automatic
carrier reduction
selection, 1st-motor
・To decrease high frequency electromagnetic noise, [bb101]
should be set small. To lower motor sound loudness, [bb101]
has to be set bigger.
・The carrier frequency may be internally limited depending on
the setting of Load type selection [Ub-03].
※(SH1-03410-H(SH1-1600H)toSH1-04810-H(SH1-2200H)support only
ND(normal duty)and LD(low duty)).
・For the sake of the inverter protection, the Automatic carrier
reduction [bb103] decreases the carrier in certain cases.
Reset operation after error event
Code/Name
bb-10
Automatic
error reset selection
bb-11
Alarm signal
selection at automatic
error reset
bb-12
Automatic
error reset wait time
bb-13
Automatic
error reset number
・Adjustment of the automatic reset that follows an error
event. In the case that RUN command was on
execution, after resetting, the motor re-operates
according to the setting of [bb-41] Restart mode after
RS release.
Retry/trip setting in error event
Code/Name
bb-20
Number of retries after
instantaneous power failure
bb-21
Number of retries after
under voltage
bb-22
Number of retries after
overcurrent
bb-23
Number of retries after over
voltage
・Set the number of times to retry after each error.
・If 0 is set, as soon as an error occurs, it will trip.
・To retry, set the value of these parameters other than 0.
4-27
[bb101] to [bb-23]
Range (unit)
・400V SH1-007H to SH1-550H
[Ub-03]=
02(ND): 0.5 to 16.0(kHz)
01(LD): 0.5 to 12.0(kHz)
00(VLD): 0.5 to 10.0(kHz)
・400V SH1-750H or above
[Ub-03]=
02(ND): 0.5 to 10.0(kHz)
01(LD): 0.5 to 8.0(kHz)
00(VLD):0.5 to 8.0(kHz)
00(Disable)/
01(Enable: Patern-1)/
02(Enable: Patern-2)/
03(Enable: Patern-3)
00(Disable)/
01(Enable: Current)/
02(Enable: Temperature)
Range (unit)
00(Disable)/
01(If RUN command is OFF)
02(After set time)
00(Enable)/
01(Disable)
0 to 600(s)
0 to 10(count)
Range (unit)
0 to 16/255
0 to 16/255
0 to 5
0 to 5
Initial
value
2.0
00
00
Initial
value
00
00
2
3
Initial
value
0
0
0
0