Chapter 2
2.2 Install the Inverter
Transportation
•
The inverter is made of plastics component. When
carrying the inverter, handle it carefully to prevent
damage to the parts.
•
Do not carry the inverter by holding the front or
terminal block cover. Doing so may cause the
inverter to fall.
•
Do not install and operate the inverter if it is
damaged or its parts are missing.
Ambient temperature
•
Avoid installing the inverter in a place where the
ambient temperature goes above or below the
allowable range defined by the standard inverter
specification.
Ambient temperature:
ND rated
: -10 to 50°C
LD rated
: -10 to 45°C
VLD rated
: -10 to 40°C
*1)
*1) SH1-03410-H(SH1-1600H)~SH1-06600-H(SH1-3150H)
support only normal duty(ND)and low duty (ND).
•
Keep sufficient space around the inverter.
Measure the temperature in a position about 5 cm
distant from the bottom-center point of the
inverter,
and
check
temperature is within the allowable range.
Operating the inverter at a temperature outside
this range will shorten the inverter life (especially
the electrolytic capacitor life), resulting in damage
to the inverter.
Do not install on a high temperature, high
humidity or easily condensation area
•
Avoid installing the inverter in a place where the
relative humidity goes above or below the range
(20% to 90% RH), as defined by the standard
inverter specification. Avoid a place where the
inverter is subject to condensation.
•
Condensation inside the inverter will result in
short circuits, which may cause damage to the
inverter. Also avoid places where the inverter is
exposed to direct sunlight.
that
the
measured
2-2
Install inverter on nonflammable
(e.g. metal) surface.
•
The inverter will reach a high temperature (up to
about 150°C) during operation. Install the inverter
on a vertical wall surface made of nonflammable
material (e.g., metal) to avoid the risk of fire.
•
In particular, keep sufficient distance between the
inverter and other heat sources (e.g., braking
resistors and reactors) if they are installed in the
vicinity.
For
SH1-00041-H~SH1-01470-H
(SH1-007H~SH1-550H)
10 cm
or more30
5 cm
5 cm
or more
or more
10 cm
or more
In order to replace life cycle parts on following models
require a clearance of 22cm or more:
•
SH1-00400-H(SH1-150H)~SH1-00620-H(SH1-220H)
In order to replace life cycle parts on following models is
required to remove the installed units:
•
SH1-00041-H(SH1-007H)~SH1-00310-H(SH1-110H)
Wall
For dimension drawing of
Air flow
Installation and Wiring
For
SH1-01760-H~SH1-06600-H
(SH1-750H~SH1-3150H)
cm
or more
5 cm
5 cm
or more
or more
30 cm
or more
•
Keep
enough
clearance
between the inverter and the
above and below wiring ducts
to
prevent
cooling
ventilation from obstructing.
inverter see chapter 2.3.
air