Chapter 2
Installation environment
Avoid installing the inverter in a place where the
inverter is subject to dust, corrosive gases,
explosive gases, flammable gases, grinding fluid
mist, or salt water.
Foreign particles entering the inverter will cause of
failure. If you use the inverter in a considerably
dusty environment, install the inverter inside a
totally enclosure.
Installation method and position
Install the inverter vertically and securely with
screws or bolts on a surface that is free from
vibrations and that can bear the inverter weight.
If the inverter is not installed properly, its cooling
performance may be degraded and tripping or
inverter damage may result.
Screw
clamp
Screw
clamp
Mounting in an enclosure
When mounting multiple inverters in an enclosure
with a ventilation fan, carefully design the layout
of the ventilation fan, air intake port, and inverters.
An
inappropriate
inverter-cooling effect and raise the ambient
temperature. Plan the layout properly so that the
inverter ambient temperature will remain within
the range specified in the specification table.
Ventilation
fan
Inverter
(Acceptable)
Position of ventilation fan
 When the inverter is installed below ventilation fan,
the incoming dust may adhere to the inverter. Place in
a position to avoid this falling dust.
Screw
clamp
Screw
clamp
layout
will
reduce
the
Ventilation
fan
Inverter
(Unacceptable)
Reduction of enclosure size
External heat sink installation may reduce internal
heat emission and reduce the enclosure size.
External heat sink mounting for the inverter
SH1-00041-H~SH1-00126-H(SH1-007H~SH1-037H)
requires an optional metal fitting.
Models other than the above can be mounted
using the brackets attached on the inverter. When
mounting the inverter with the heatsink outside
the
enclosure,
depending on the panel cut
The cooling section (including the heat sink)
positioned outside the enclosure has a cooling fan.
Therefore, do not place the enclosure in any
environment where it is exposed to water drops,
oil mist, or dust.
The heat sink part reaches a high temperature.
Install a protection cover as needed.
■Watt loss (W) (at 100% load, approximate)
*400V class
SH1-*****-H
00041 00054 00083 00126 00175 00250 00310 00400
SH1-***H
007
015
62
94
ND
Watt
67
98
loss
LD
(W)
VLD
76
104
SH1-*****-H
00470 00620 00770 00930 01160 01470 01760 02130
SH1-***H
185
220
495
687
ND
Watt
601
805
loss
LD
(W)
VLD
633
860
SH1-*****-H
02520 03160 03410 03950 04460
SH1-***H
1100 1320 1600 1850 2000
2219 3872 3896 4091 4514
ND
Watt
2397 4352
loss
LD
(W)
2557 4598
VLD
(Note: These data are reference values of our site and vary
depending on the power supply environment and the
motor power factor.)
2-3
Installation and Wiring
cut
the
mounting
dimensions.
022
037
055
075
110
96
145
235
240
260
107
163
260
280
306
134
189
290
306
380
300
370
450
550
750
783
812 1047 1130 1570 2034
854
880 1218 1488 1811 2150
920
971 1300 1592 2020 2359
04810 05500 06600
2200 2500 3150
4710 5750 7545
4379 4598 4622 5251 6250 7875
surface
150
361
444
482
900