Message Assignment - Zone Specific - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

Programmed Activation by FACP

Message Assignment - Zone Specific

The FACP can be programmed to allow a specific addressable input device to generate one of five
messages over any speaker circuit. Any one of the five messages can be programmed to each of the
available zones (Zone 1 through Zone 99). In the following examples, assume that Zone 5 is pro-
grammed to Message 1, Zone 7 is programmed to Message 2, Zone 8 is programmed to Message 3,
and Zone 35 is not programmed to a message.
if two devices are being programmed and the first addressable input device is programmed to
Zone 7 and Zone 35, and a second addressable input device is programmed to Zone 5 and Zone
35, activation of the first addressable input device (address 12 in the example below) will
cause Message 2 to be generated over speaker circuit 3. (Table D.5 on page 109). If the sec-
ond addressable device (address 20 in the example below) is also activated, Message 1 will
now be transmitted over speaker circuit 3 since Message 1 has a higher priority then Message
2.
programmed to
Addressable Pull Station
(address 12)
programmed to
Addressable Pull Station
(address 20)
Programming is accomplished in the same manner as previously described.
To Program one of five messages to a speaker zone, press the ENTER key at the FACP. The
following screen will be displayed:
112
Zone 7
and
Zone 35
Message 2
(2nd highest priority of the three)
Zone 5
and
Zone 35
Message 1
(highest priority of the three )
1=READ STATUS MODE
2=PROGRAMMING MODE
3=MANUAL DIAL MODE
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
MS-9600, MS-9200UDLS and MS-9200UD
activate
Speaker Circuit 3
activate