Appendix B: Addressable Module Connections

When configured with an addressable FACP such as the MS-9200UDLS, MS-9200UD,
MS-9200C(E), or MS-9600, the AUDIO•COMMAND•CENTER•25/50 Series may be triggered
either by the FACP main NAC output or from addressable control modules. Figure B.1 illustrates
CMD1 triggered by an addressable control module. The addressable control module may trigger
the ACC-25/50 Series via reverse polarity (shown) or relay contact. The FACP monitors the ACC-
25/50 Series for faults while in the standby or alarm state by wiring a monitor module to the trouble
contacts as shown in Figure B.1. Activation of the addressable control module is controlled by the
FACP. Refer to the MS-9200UDLS, MS-9200UD, MS-9200C(E), or MS-9600 manual for addi-
tional information.
Specific
Application
4.7K ELR
Power
PN: 27072
Note 1
TB7
TB6 TB4
MASTER
CMD OUT
P12
CHGR DISABLE
P4
P1
CB1
TB3
- +
AC HOT NEUT EARTH
BATTERY
Notes:
1.
Auxiliary Power terminals for special application power only. Wiring must remain in the
room.
2.
Supervise the wiring between the ACC-25/50 Series Auxiliary Power output and the control
module with an EOL relay (EOLR-1).
3.
End-of-Line resistor supplied with modules.
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
-
T11
T10
+
T9
T8
Output
+
T7
T6
-
Output
EOL Power Supervision
Note
Relay (EOLR-1)
3
Note 2
-
+
AUX
CMD1
CMD2
CMD3 IN
POWER
PRIMARY AMP
P11
P10
ZONE PAGE MODULE
Figure B.1 Addressable Module Connections
24 VDC
T1
SLC
T2
T3
T4
T5
Control
Module*
Note
3
4.7K ELRs PN: 27072
CMD4 IN
CMD5 IN
TROUBLE
RELAY
SECONDARY AMP
P3
EXT.AUDIO
INPUT
EXT.AUDIO
INPUT
P9
ZONE PAGE MODULE
PLAYBACK
T11
T10
T1
T9
T2
T8
T3
T7
T4
T6
T5
Monitor
Module*
*
If the SLC device does not match the
one in this figure, refer to the SLC
manual devices wiring conversion
charts for the legacy and newer type
modules.
JP1
O N
AC PWR
S3
1 2 3 4 5 6 7 8
BATT TBL
O N
S5
CHG TBL
1 2 3 4 5 6 7 8
O N
GND FLT
S1
1 2 3 4 5 6 7 8
REMOTE
MIC INPUT
ZONE 1
S2
MESSAGE 1
P2
LOCAL
SLC
P5
P13
EXT PAGE
INPUT
POWER ON
SYSTEM
TROUBLE
MESSAGE
TROUBLE
GENERATOR
P1
TONE
GENERATOR
TROUBLE
MICROPHONE
TROUBLE
RECORD
PLAYBACK
TROUBLE
SILENCE
P6
MICROPHONE
103

Advertisement

Table of Contents
loading

Table of Contents