Table of Contents

Advertisement

Master Programming Level
3.5.3 Zone Setup
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2

Zone Types

ZONE SETUP
1=ZONE TYPES

2=ZONE MESSAGE

3=SPECIAL PURPOSE
Zone Setup Screen #3
This display will show the system zones (default and user programmed) and their associated types. Note that an up and/or down arrow will
appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys
to view zones Z000 through Z255.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each Zones Installed Screen. Available zone
types will be displayed in the resultant screens. For example, to change the zone type for zone Z002 in the screen illustrated above, press 3.
The following screens will be displayed:
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON.
3=SMOKE ION
Zone Type Program Screen #4
To change the zone type for Z002 to Pull Station, scroll the display until Zone Type Program Screen #2 is displayed. Press 2 to program zone
Z002 as a Pull Station zone. The display will return to the Zones Installed Screen showing zone Z002 and the Pull Station program type.
Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable zone type to the selected
zone. Any signaling devices programmed to the same zone can be silenced by pressing the Alarm Silence key or by using the auto-silence fea-
ture.
To program a waterflow circuit as non-silenceable, refer to "System Setup" on page 67.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central
Station.
Zone Message
This feature is not available at this time.

Special Purpose Zone

Pressing 3 for Special Purpose, while viewing Zone Setup Screen #1, will display the following screens:
Zones 250, 251, 252, 253, 254 and 255 can be programmed for normal zone operation or for special purpose applications. In the above illus-
tration, the four zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning
them to input and output devices in the Programming Zone Assignment Screen.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated below:
ZONE SETUP
1=ZONE TYPES
2=ZONE MESSAGE
3=SPECIAL PURPOSE
Zone Setup Screen #1
Zone Types must be programmed only if a Communicator, programmed for zone reporting, is installed on the
control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #1, will display a screen similar to
the following:
ZONE TYPE PROG
1=Z000
2=Z001
3=Z002
Zones Installed Screen
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG
1=CO ZONE
2=NONE
Zone Type Program Screen #5
SPECIAL PURPOSE
1=PAS 253
OFF
2=PRE-SIGNAL 254 OFF
3=TWO STAGE 255
OFF
Special Purpose Zone Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
MONITOR
MONITOR
MONITOR
SPECIAL PURPOSE
1=LOCAL ALM 252
2=CO ACTIVE 251
3=INSUITE SIL 250 OFF
Special Purpose Zone Screen #2
Programming
ZONE SETUP
1=ZONES AVAILABLE
Zone Setup Screen #3
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
OFF