Appendix C: Wiring Requirements - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

Appendix C: Wiring Requirements

Connecting external system accessories to the AUDIO•COMMAND•CENTER•25/50 Series main
circuits must be carefully considered to ensure proper operation. It is important to use the correct
type of wire, wire gauge and wire run length per each circuit. Refer to the following table to spec-
ify wire requirements and limitations.
NOTE: If an SLC loop is to be run in conduit with AUDIO•COMMAND•CENTER•25/50 Series
Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by using
twisted, shielded cable on the SLC and NACs.
CIRCUIT CONNECTIONS
Circuit Type
AC Power
Primary Power Input to
TB3 (nonpower-limited)
Audio Output
Notification Appliance Circuit
ACC-AAM25 Module
TB1 and
ACC-ZSM Module
(power-limited)
ACC-ZPMK Module
ACS (EIA-485 Circuit
ACC-FFT TB1
ACC-FFT TB2
ACC-FFT TB3
Remote Microphone
ACC-EPM Module
External Page Connection
CMD1 and CMD2 Main
Triggers ACC-25/50 Series
Board TB2 and TB5
CMD3, CMD4 and
Triggers ACC-25/50 Series
CMD5 Main Board TB8,
TB9 and TB10
Main Board TB6 Master
Output Trigger for Multiple
Command Bus Reverse
Polarity (power-limited)
Trouble Relay Main
Board TB1
AC Loss Relay
Main Board TB7
Table C.1 AUDIO•COMMAND•CENTER•25/50 Series Wiring Requirements
1 Refer to NEC Standards.
2 Twisted, shielded wire is recommended for maximum protection against EMI and AFI emissions and susceptibility.
3 Must also meet NFPA 72 Standards for minimum and maximum sound levels.
4 Refer to Remote Microphone Document #51247.
104
Wire Type &
Circuit Function
Limitations
ACC-25/50 Series,
AC Voltage
unshielded or
twisted, shielded
Telephone Loop
unshielded or
twisted, shielded
Contact Closure
Input Trigger
4
Connection
unshielded or
twisted, shielded
unshielded or
twisted, shielded
ACC-25/50 Series
configurations
Trouble Output
Current 2 amps
AC Loss Output
Current 2 amps
WIRE REQUIREMENTS
Recommended Maximum Distance
1
See Note
Power Supplied must be:
120 VAC, 60 Hz, 1.5 amps (see Note
2
See Note
Untwisted,
2
See Note
54 maximum impedance
Untwisted
Untwisted
54 maximum impedance
unshielded
4
See Note
1
See Note
Depends on Output (trigger) Circuit
Untwisted,
9 - 32 VDC, 1.6 mA for polarity reversal
relay must be rated at 0.5 amp, 24
1
See Note
Depends on Output (trigger)
Untwisted,
Circuit from contact device
Untwisted,
200 ohms maximum
unshielded
Maximum
Depends on Input Circuit
Maximum
Depends on Input Circuit
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
(Feet)
Terminals Support
1
)
3
See Note
4,000 feet
4
See Note
VDC
Wire Gauge
12-18 AWG
1
(see Note
)
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG
4
See Note
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG
12 - 18 AWG

Advertisement