3: General Zone - Honeywell NOTIFIER NFS2-3030 Programming Manual

Fire alarm control panel
Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Point Program
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.
NOTE:
will not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL.
FORM C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET.
The FMM-1 module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate
in Walk Test.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:
NO
YES - RESOUND FIRE
YES - RESOUND SUPERV
YES - RESOUND SECURITY
YES - RESOUND TROUBLE
YES - NO RESOUND
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel's SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with"fire" point types will activate SLC outputs with"fire"
point types. Refer to Appendix G.3, "Type Codes for Input Devices", on page 127 for Type Code
point types. Default: OFF
NOTE: The panel setting
device level.
3.4.3 General Zone
This screen displays when a general zone is chosen at the Point Program menu (see Figure 3.24 on
page 39).
NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key
Not manually silenceable
Silenceable, resound on fire alarm events
Silenceable, resound on supervisory events Network and Local Resound
Silenceable, resound on security events
Silenceable, resound for trouble
Silenceable, does not resound
LCM LOCAL MODE
Network and Local Resound
Network and Local Resound
Local Resound
must be set to Yes for local mode to work at the
Program
49