Acc-25/50Zs And Acc-25/50Zst Switch Settings; Acm-8Rf Programming; Ms-5210Ud Programming - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

MS-5210UD
Connect CMD inputs of ACC-25/50ZS/T to
Normally Open relay contacts of the ACM-8RF.
-
-
+ +
-
+
TB2
TB6
1 2 3 4
1 2 3 4
MASTER
CMD1
CMD OUT
ACC-

ACC-25/50ZS and ACC-25/50ZST Switch Settings

ACC-ZPMK Zone Page Module DIP Switch S1
Switches 1, 2, and 3 are set to OFF, OFF, OFF for No ACS link operation
Switch 4 (future use) is set to OFF
Switches 5, 6, 7, and 8 are set to OFF
ACC-ZSM Zone Splitter Module Switch Settings (refer to Section "ACC-ZSM Zone Splitter Mod-
ule (ACC-25/50ZS & ACC-25/50ZST)" on page 41 for additional information).
ACC-25/50ZS/T Main Board DIP Switch S3
The following DIP Switches can be set to any value except 1, 2, 3 = OFF, OFF, OFF.
Switches 1, 2, and 3 are set to ON, OFF, ON for Single Zone output and the selection of five
messages

ACM-8RF Programming

Set rotary switch on ACM-8RF for ACS address 1
Assign SW3 DIP Switch settings per MS-5210UD manual

MS-5210UD Programming

Assign functions (alarm, supervisory, etc.) to Zones 1 through 5 for voice message control.
Enable the LED-10IM EIA-485 Interface Module.
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
-
-
-
-
+
+
-
+
+
+
+
-
-
+
TB9
TB5
TB8
1 2 3 4
1 2
1 2
CMD2
CMD3
CMD4
(Alarm Polarities Shown)
25/50 Series Main Circuit Board
ALL-CALL
POWER ON
SYSTEM
AUDIO
TROUBLE
ON/OFF
MESSAGE
TROUBLE
FIRST ALERT
GENERATOR
MESSAGE
TONE
GENERATOR
TORNADO
TROUBLE
MESSAGE
MICROPHONE
TROUBLE
CHEM SPILL
MESSAGE
RECORD
PLAYBACK
ALL CLEAR
TROUBLE
MESSAGE
SILENCE
Figure D.4 ACC-25/50ZS/T Connection to ACM-8RF
1 2
-
-
+
+
TB10
1 2
ACM-8RF
CMD5
-
-
+
+
TB1
TB2
FACP Comm
ACC Comm
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
S1
ON
TENS ONES
S1
O N
1 2 3 4 5 6 7 8
S3
S2
ACC-
ZPMK
Programmed Activation by FACP
4.7K ELRs, P/N: 27072
1
2
3
4
5
6
7
8
O
F
F
121