16 Theater Cineplex Utilizing ACC-25/50ZS With ACC-25/50DAZS

5.7 16 Theater Cineplex Utilizing ACC-25/50ZS With ACC-
25/50DAZS
In this application, the Fire Protection System consists of one ACC-25/50ZS with one ACC-
25/50DAZS, 16 zones and an addressable FACP. Each one of the 16 movie theaters is wired and
assigned as a speaker circuit. The FACP is programmed for Software Zone 33 for Theater 1
through Software Zone 49 for Theater 16. Software Zone 32 is programmed to activate all speaker
circuits (All-Call). In addition, the Fire Evacuation Message (Message #1) is entered into Software
Zones 32 - 49.
Automatic control by the FACP is provided through the ACS link to the ACC-25/50ZS. Manual
control is possible via the keypad in the ACC-25/50ZS. Control of Audio Zones 9 - 16 is sent
through the ACC Control Serial Link to the ACC-25/50DAZS. Alarm and Paging audio from the
ACC-25/50ZS is delivered to Audio Zones 9 - 16 (ACC-25/50DAZS) by way of the Audio Riser.