D.1.3: Wiring From Acc-25/50Zs Or Acc-25/50Zst To Facp - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

MS-9600, MS-9200UDLS and MS-9200UD
3.
Set DIP Switches 1, 2, and 3 on Switch S1 of the ACC-ZPMK for operation with the MS-9600,
MS-9200UD, MS-9200UDLS FACP and switches 6, 7, and 8 for the number of ACC-
25/50DAZS panels.
4.
Set Switch SW1 on the ACC-ZSM for one or two Audio Amplifier (ACC-AAM25)
configuration.
5.
Set Switch SW2 on the ACC-ZSM for Style Y (Class B) or Style Z (Class A) speaker circuit
wiring.
6.
Set DIP switches 1, 2, and 3 on Switch S3 of the ACC-25/50ZS or ACC-25/50ZST
motherboard for Single Zone with activation of 2-5 messages.
7.
Record any new messages into the ACC-25/50ZS or ACC-25/50ZST.
8.
Enable ACS communication to address 01 and assign messages (1-5) to audio zones (32-56) in
the FACP.
9.
ACC-25/50ZST with remote FFT location annunciation:
D.1.3 Wiring From ACC-25/50ZS or ACC-25/50ZST to FACP
MS-9600 and MS-9600LS
The FACP communicates with the ACC-25/50ZS/T over the ACS or ANN-BUS annunciator link.
Wiring must be connected between Terminal TB6 on the FACP and Terminal TB1 on the ACC-
ZPMK Zone Page Module installed on the ACC-25/50ZS/T panel.
ANN
A
B
ACS
MS-9600 or MS-9600LS
Figure D.1 Connection for MS-9600 or MS-9600LS to ACC-ZPMK
MS-9200UD and MS-9200UDLS
The MS-9200UD and MS-9200UDLS FACPs communicate with the ACC-25/50ZS or ACC-
25/50ZST over the ACS or ANN-BUS annunciator link. Wiring must be connected between Ter-
minal TB9 on the FACP and Terminal TB1 on the ACC-ZPMK Zone Page Module installed on the
ACC-25/50ZS or ACC-25/50ZST panel.
ANN
A
B
ACS
+
-
TB8
TB9
TB10
ACS
OUT+ IN+ OUT- IN-
ACS
MS-9200UD or MS-9200UDLS
Figure D.2 Connection for MS-9200UD or MS-9200UDLS to ACC-ZPMK
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
MS-9200UDLSMS-9200UDLS - Enable ACS address 07 or address 05 (for version 4 and
higher) and program SLC points 75-98.
MS-9600 - Enable ACS address 07 and program SLC loop #1 points 135-158.
SLC
SLC
SHIELD
SLC
SLC
B+ A+ B- A-
A
B
Programmed Activation by FACP
to other ACS/ANN
devices
ACC-ZPMK
to other ACS/ANN
devices
+ +
- -
1 2 3 4
TB2
TB1
ACC-ZPMK
107