D.4.3: Acc-Zpmk Dip Switch 1 Settings On Acc-25/50Zs And Acc-25/50Zst - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

Programmed Activation by FACP
D.4.3 ACC-ZPMK DIP Switch 1 Settings on ACC-25/50ZS and
ACC-25/50ZST
Switches 1, 2, and 3 are used to configure the ACC-25/50ZS and ACC-25/50ZST for operation
with a specific FACP. The switch settings for use with the MS-5UD-3/7 and MS-10UD-3/7 (soft-
ware version 2.0 or higher) are as follows:
Switch 1
ON
Table D.8 MS-5UD-3/7 and MS-10UD-3/7 FACP Configuration
128
Switch 2
Switch 3
ON
OFF
Configuration
MS-5UD-3/7 and MS-10UD-3/7 Version 2.0 or higher
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
MS-5UD-3/7 and MS-10UD-3/7