Acc-25/50Zs/T Dip Switch Settings - Honeywell Fire-Lite Alarms ACC-25/50 Instruction Manual

Voice evacuation control panels
Table of Contents

Advertisement

MS-5210UD
If only the generating Fire Evacuation announcement (Message #1) to individual audio zones is
desired, do not connect the MS-5210UD Relay outputs to the ACC-25/50ZS or ACC-25/50ZST
CMD inputs. In this case, the activation of the audio zones via the ACS link will automatically trip
the Fire Evacuation message to the ACS link selected zone.
Manually deactivating a speaker circuit is accomplished by pressing the activated zone push-button
on the ACC-ZPMK keypad. Manual activation of the audio system can be performed by selecting
zone push-buttons(s) on the ACC-ZPMK and then pressing either of the Message buttons. All-Call
Paging is possible by first pressing the All-Call push-button on the ACC-25/50ZS or
ACC-25/50ZST main keypad and then pressing the push-to-talk switch on the microphone.
All faults on the ACC-25/50ZS or ACC-25/50ZST are sent upstream via the ACS link to the MS-
5210UD and are indicated by illuminating the System Trouble LED on the MS-5210UD.
24V
24V NON
RESETTABLE
RESETTABLE
RELAY 1
TB2
Figure D.3 MS-5210UD Connection to ACC-25/50ZS or ACC-25/50ZST

ACC-25/50ZS/T DIP Switch Settings

ACC-ZPMK Zone Page Module DIP switch S1:
Switches 1, 2, and 3 are set to OFF, OFF, ON for ACS link operation with the MS-5210UD
FACP
Switch 4 (future use) is set to OFF
Switch 5, 6, and 7 are set to OFF
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
4.7K ELRs, P/N: 27072
-
-
-
-
+ +
+
+
TB5
TB2
TB6
1 2 3 4
1 2 3 4
MASTER
CMD1
(Alarm Polarities Shown)
CMD OUT
ACC-25/50 Series Main Circuit Board
ALL-CALL
AUDIO ON/OFF
FIRE
MESSAGE
GENERATOR
GENERATOR
CHEM SPILL
MICROPHONE
ACC-25/50ZS/T
Keypad
4.7K ELRs, P/N: 27072
BELL 2
RELAY 2
BELL 1
TB5
TB3
TB4
MS-5210UD
4.7K ELRs, P/N: 27072
-
-
-
-
+
+
-
-
+
+
+
+
TB8
TB9
TB10
1 2
1 2
1 2 3 4
CMD2
CMD3
CMD4
POWER ON
SYSTEM
TROUBLE
MESSAGE
TROUBLE
TONE
-
-
+
+
TROUBLE
TROUBLE
TB1
TB2
RECORD
PLAYBACK
TROUBLE
FACP Comm
ACC Comm
SILENCE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ON
S1
TENS ONES
S1
ON
1 2 3 4 5 6 7 8
S3
ACC-ZPMK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
J10
CLASS A CONVERTER MOD
Programmed Activation by FACP
+
+
-
-
1 2
CMD5
to other ACS devices
located down stream
Address 01
S2
Set S2=1
Set S3=0
+ -
+ -
ZONE 9
ZONE 10
TB1
J1
J6
KED-10IM INTERFACE
MODULE
119