This control panel has been designed to comply with standards set forth by the following regulatory agencies:
Underwriters Laboratories Standard UL 864
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have
minimum sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA
at the minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at
least 15 dBA above the average ambient sound level or 5 dBA above the maximum sound
level with a duration of at least 60 seconds, depending on which level is greater, with the
sound level being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document
MS-5UD/10UD Series Technical Manual
FCPS-24F(E) Field Charger/Power Supply
FCPS-2404 Field Charger/Power Supply
FCPS-24FS6/8 Field Charger/Power Supply
MS-9200(C/E) Technical Manual
MS-9200UD Technical Manual
MS-9200UDLS Technical Manual
MS-9600 Technical Manual
MS-5210UD Technical Manual
ACC-25/50DA Technical Manual
SLC Wiring Manual
Document #15384
Document #52626
Document #50079
Document #51486
Document #51883
Document #51003
Document #51906
Document #52750
Document #51335
Document #50193
Document #52265
Document #51309