D.1.4 ACC-25/50ZS and ACC-25/50ZST Switch Settings
ACC-ZPMK DIP Switch S1
Switches 1, 2, and 3 are used to configure the ACC-25/50ZS and ACC-25/50ZST for operation
with a specific FACP as shown in the following table:
SWITCH
SWITCH
1
2
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
Switch 4 - future use
Switches 5, 6, 7, and 8 - used to set the number of ACC-25/50DAZS panels installed.
S1 DIP Switch
5
6
This switch works in conjunction with switches 7 & 8 to set the number of ACC-25/50DAZS panels connected
7
This switch works in conjunction with switches 6 & 8 to set the number of ACC-25/50DAZS panels connected
8
6 OFF, 7 OFF, 8 OFF = No ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 OFF, 8 ON = 1 ACC-25/50DAZS Distributed Audio Panel connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 OFF = 2 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 OFF, 7 ON, 8 ON = 3 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 OFF = 4 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
6 ON, 7 OFF, 8 ON = 5 ACC-25/50DAZS Distributed Audio Panels connected to ACC-25/50ZS/T
Table D.3 Number of ACC-25/50DAZS Panels Installed
ACC-ZPMK Rotary Address Switches S2 and S3
ACS Protocol:
The address switches must be set to ACS address 01 to communicate with the FACP. Any other
ACS devices which are set to address 01 should be in Receive Mode only.
S2=1
S3=0
ANN-BUS Protocol:
The address switches can be set to any address between 01 through 08 to communicate with the
FACP. Any other ANN-BUS devices must be set to a different address.
S2=1-8
S3=0
ACC-ZSM Zone Splitter Module Switch Settings
See "ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)" on page 41 for infor-
mation on setting these switches.
ACC-FFT Fire Fighter Module Switch Setting (ACC-25/50ZST only)
See Section "SW1 - Remote Microphone Installed Switch on ACC-FFT" on page 39 for additional
information.
108
SWITCH
CONFIGURED FOR OPERATION WITH FOLLOWING FIRE ALARM
3
OFF
ON
OFF
ON
ACS Protocol: MS-9200UDLS or MS-9200UD version 2 or higher
OFF
Table D.2 FACP Configuration
ON
not used (must be set to OFF)
Audio Command Center Series Manual — P/N 51889:E1 6/8/2010
MS-9600, MS-9200UDLS and MS-9200UD
CONTROL PANEL
MS-9200UD version 1
ACS Protocol: MS-9600 version 1
ACS Protocol: MS-9600 version 2 or higher
ANN-BUS Protocol:
MS-9600LS Version 4 or higher
MS-9200UDLS Version 4 or higher
OFF