Field Settings for Indoor Unit
1.4.37 Setting Restricted/Permitted of Airflow Block
The airflow block function cannot be enabled when closure material kit, fresh air intake kit,
separately installed natural evaporation type humidifier, or branch air duct is equipped, due to
the possibility of dew condensation.
This setting restricts the airflow block function, preventing that the airflow block is inadvertently
set to ON.
Ensure that "Airflow block restricted" is set when using the options listed above.
Mode
1.4.38 Room Temperature Display
 BRC1E Series
A "Detailed display screen" can be selected as the display screen. This setting is used if you do
not want to display "Room temperature display" on the "Detailed display screen".
1.5

Operation Control Mode

The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote controller. Furthermore, operations such as remote
controller ON/OFF can be limited in accordance with the combination conditions. (Refer to
information on the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor
is connected)
Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
 ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
 OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller
only.
 Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
 Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
 Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
106
First
Second
No.
Code No.
Code No.
01
02
1b
14
03
04
05
Mode
First
Second
No.
Code No.
Code No.
01
1c
0
02
Contents
Airflow block permitted
Airflow block restricted
Contents
Not displayed
Displayed
Part 5 Field Settings and Test Operation
SiME332106E
: Factory setting
: Factory setting