Troubleshooting by Error Code
5.32 Refrigerant Overcharged
Applicable
All outdoor unit models
Models
F6
Error Code
Method of Error
Detect overcharged refrigerant according to outdoor air temperature, heat exchanger liquid pipe
Detection
temperature, and subcooling liquid pipe temperature during test operation.
Error Decision
When the amount of refrigerant, which is calculated using outdoor air temperature, heat
Conditions
exchanger liquid pipe temperature, and subcooling liquid pipe temperature during test
operation, exceeds the regular charge amount by 30% or more
(If refrigerant is charged slightly over the regular charge amount, F6 may be displayed on the
remote controller.)
Supposed
Refrigerant overcharged
Causes
Disconnection of outdoor air thermistor
Disconnection of heat exchanger liquid pipe thermistor
Disconnection of subcooling liquid pipe thermistor
Troubleshooting
Reference
CHECK 11 Refer to page 281.
210
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check for the conditions of
mounting of the temperature
sensors of the outdoor air
thermistor, the heat exchanger
liquid pipe thermistor, and
subcooling liquid pipe thermistor
to the piping.
Are the temperature
sensors properly
mounted?
YES
Disconnect the outdoor air
thermistor, the heat exchanger
liquid pipe thermistor, and
subcooling liquid pipe
thermistor from the outdoor
unit main PCB, and then make
measurement of resistance
using a multimeter.
CHECK 11
Normal?
YES
NO
NO
SiME332106E
Properly connect the thermistors,
and then operate the system.
Replace abnormal thermistors,
and then operate the system.
Remedy refrigerant overcharging.
Part 6 Service Diagnosis