Reactor Temperature Abnormality - Daikin VRV RXYMQ-A Series Service Manual

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

Troubleshooting by Error Code

5.49 Reactor Temperature Abnormality

Applicable
RXYMQ4-6AYFK
Models
P3
Error Code
Method of Error
Detect according to the value detected with the reactor surface thermistor.
Detection
Error Decision
When the system is in operation and the thermistor causes wiring disconnection or short circuit
Conditions
in it.
Supposed
 Defective connection of thermistor
 Defective reactor surface thermistor
Causes
 Defective inverter PCB
Troubleshooting
236
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Make measurement of
resistance of the radiation
fin thermistor.
Is the
resistance of the
thermistor normal?
YES
Turn ON the
power supply.
Does the error
recur?
NO
NO
YES
SiME332106E
Replace the inverter PCB (A3P).
Replace the inverter PCB (A3P).
Continue operation.