Protection Control
6.5
Heating Operation Prohibition
When outdoor air temperature becomes high, outdoor unit cannot perform heating because:
Heating is disabled when outdoor air temperature rises above 27°C.
Heating returns available when outdoor air temperature drops below 25°C.
6.6
Overload Protection Control
Prevent ignition due to abnormal heating of the compressor when it becomes damaged or
abnormal operation.
64
Low pressure sensor can give pressure value above upper limit of sensor: error JC.
Mechanical internal load on compressor increases.
Low compression ratio can result in insufficient compressor internal oil lubrication.
Forced thermostat-OFF indoor units.
Outdoor fan operates at step 1.
Compressor body temp.
Normal control
t 125 °C
Overload standby
(Error code F3 is output)
SiME332106E
Compressor body temp. d 110 °C
&
Remote controller resets.
Part 4 Functions and Control