SiUS331604E
(35) Setting "Restricted / Permitted" for Airflow Block
(For Sensing flow type only)
Due to possibility of dew condensation, the airflow block function cannot be enabled when closure material kit,
fresh air intake kit, natural / separately installed evaporation humidifier, or branch air duct is equipped.
This setting will prevent the airflow bock is advertently set to ON.
Ensure that this setting is "Disable airflow block" when using together with options listed above.
Mode No.
1b (2b)
(36) Room Temperature Display
(For BRC1E73 only)
A "Detailed display screen" can be selected as the display screen. This setting is used if you do not want "Room
temperature display" to be shown on the "Detailed display screen."
Mode No.
1c (2c)
2.4
Outdoor-Air Processing Unit - Field Setting
(Remote Controller)
First
Mode
Setting Contents
Code
No.
No.
0
Filter contamination
10
Display time to
(20)
3
clean air filter
calculation
External ON/OFF
1
input
12
(22)
Power failure
5
automatic reset
Discharge
14
pipe
3
(24)
temperature
(cooling)
2.5

Field Setting of Operation Control Mode

The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Centralized remote controller is normally available for operations. (Except when centralized monitor is
connected)
Field Setting
Second Code
First Code No.
No.
01
02
14
03
04
05
Second Code
First Code No.
No.
01
0
02
01
02
2500 hr
1250 hr
No
Display
display
Forced
ON/OFF
OFF
control
Not
Equipped
equipped
°C
13
14
°F
55.4
57.2
Airflow block permitted
Airflow block restricted
Room temperature is not displayed.
Room temperature is displayed.
Second Code No.
03
04
05
06
07
15
16
17
18
19
59
60.8 62.6 64.4 66.2
Field Setting from Remote Controller
Contents
Contents
08
09
10
11
12
20
21
22
23
24
68
69.8 71.6 73.4 75.2
: Factory setting