Daikin VRV RXYMQ-A Series Service Manual page 169

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

SiME332106E
Note(s)
Part 6 Service Diagnosis
A
The drain
pump works when the
power supply is reset for the
indoor unit.
NO
The
voltage of
drain pump
terminals (∗2) is in
accordance to the criteria
(∗3) (within 5 minutes of
resetting the power
supply).
YES
1: Float switch (S1L) /
Model
short circuit connector
FXFSQ-AR
X15A
FXDQ-PD
X8A
FXDQ-ND
X8A
FXMQ-PB
X15A
FXMQ-AR
X8A
YES
NO
2: Drain pump (M1P)
connector
X25A
X25A
X25A
X25A
Y1, Y2
Troubleshooting by Error Code
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit control
PCB (A1P).
Replace the drain pump or
check for dirt, etc.
3: Drain pump (M1P)
Note
voltage
13 VDC
220-240 VAC
220-240 VAC
13 VDC
220-240 VAC
163