Daikin VRV RXYMQ-A Series Service Manual page 295

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

SiME332106E
FXDQ-PD, FXDQ-ND
FXMQ-AR
FXAQ-AR
Part 6 Service Diagnosis
White (1)
φ1
Red (6)
M
φ3
Orange (3)
φ2
φ4
Yellow
(2)
(1) White
(2) Yellow
(3) Orange
(4)
Blue
(5) —
(6) Red
White (1)
I1
M
Red (6)
I3
Orange (3)
I2
I4
Yellow
(2)
Blue
Orange
(4)
(5)
(3)
(2)
(6)
(1)
Yellow
Red
White
White (1)
I1
Red (5)
M
I3
Orange (3)
I2
I4
Yellow
Brown
Blue
(2)
(6)
(1) White
(2) Yellow
(3) Orange
(4) Blue
(5) Red
(6) Brown
Measuring points
1-2
1-3
1-6
2-4
2-6
Blue
(4)
Measuring points
1-2
1-3
1-6
2-4
2-6
Blue
(4)
Measuring points
1-2
1-3
1-5
2-4
2-6
(4)
Check
Judgment criteria
No continuity
92 Ω
46 Ω
92 Ω
46 Ω
Judgment criteria
No continuity
300 :
150 :
300 :
150 :
Judgment criteria
No continuity
300 :
150 :
300 :
150 :