Daikin VRV RXYMQ-A Series Service Manual page 288

R-410a heat pump 50/60 hz
Table of Contents

Advertisement

Check
temperature
Drawing No.
282
Thermistor
Type A
(°C)
–30
363.8
–25
266.8
–20
197.8
–15
148.2
–10
112.0
–5
85.52
0
65.84
5
51.05
10
39.91
15
31.44
20
24.95
25
19.94
30
16.04
35
12.99
40
10.58
45
8.669
50
7.143
55
5.918
60
4.928
65
4.123
70
3.467
75
80
85
90
95
100
105
3SA48002
3SA48018
3S480003
(AD94A045)
Resistance (k)
Type B
361.7719
265.4704
196.9198
147.5687
111.6578
85.2610
65.6705
50.9947
39.9149
31.4796
25.0060
20.0000
16.1008
13.0426
10.6281
8.7097
7.1764
5.9407
4.9439
4.1352
3.4757
2.9349
2.4894
2.1205
1.8138
1.5575
1.3425
1.1614
3SA48001
3P283292
(AD87A001)
This data is for reference purposes only.
Part 6 Service Diagnosis
SiME332106E
Type C
111.8
85.42
65.80
51.07
39.97
31.51
25.02
20.00
16.10
13.04
10.63
8.711
7.179
3SA48016
(AD100008)
3S480014
(AD150384)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents