Details of Field Settings for Indoor Unit

1.4.1 Filter Cleaning Sign Interval, Filter Type
When the setting 10 (20)-3 is set to 01 (Displayed), filter cleaning sign is displayed on the
remote controller after a certain period of operation time. This setting is used to change the
display interval of filter cleaning sign when the filter contamination is heavy.
The filter cleaning sign interval is determined as follows depending on the combination of Mode
No. 10 (20)-0 and 10 (20)-1.
Filter cleaning sign interval
Setting
Model
1.4.2 Remote Controller Thermistor
Select a thermistor to control the room temperature.
 When the unit is not equipped with an infrared floor sensor:
10 (20)
The factory setting for the Second code No. is 01 and room temperature is controlled by the
suction air thermistor for indoor unit and remote controller thermistor. When the Second code
No. is set to 02, room temperature is controlled by the suction air thermistor. When the Second
code No. is set to 03, room temperature is controlled by the remote controller thermistor.
Part 5 Field Settings and Test Operation
10 (20)-1
Filter contamination
heavy/light 10 (20)-0
FXFSQ-AR
FXDQ-PD
FXDQ-ND
FXMQ-PB
FXMQ-AR
FXAQ-AR
Mode
First Code
Second
No.
No.
Code No.
01
2
02
03
01: Long life filter
Light
Heavy
01
02
2,500 hrs.
1,250 hrs.
200 hrs.
100 hrs.
Contents
Remote controller thermistor and suction air thermistor
in indoor unit
Suction air thermistor
Remote controller thermistor
Field Settings for Indoor Unit
: Factory setting
02: Ultra long life filter
Light
Heavy
01
02
10,000 hrs.
5,000 hrs.
200 hrs.
100 hrs.
: Factory setting
93