en | wLSN Devices
Testing the Detector (Flex and Audio Signals)
1.
2.
3.
4.
5.
Exiting from Test Mode
To exit from the Test Mode locally:
1.
2.
3.
To exit from the Test Mode remotely:
1.
2.
3.
F01U138553 | 01 | 2010.05
Set the 13-332 Tester switches to the TEST and FLEX
positions (Items 1 and 3, Figure 5.21, Page 53).
Press the red Start button (Item 2, Figure 5.21, Page 53).
The tester activates and starts an 8-sec armed period.
If window coverings are present, close them completely.
Hold the 13-332 Tester near the point on the glass farthest
from the detector. If window coverings are present, hold
the tester between the glass and window coverings.
Carefully strike the glass with a cushioned tool. The 13-332
Tester responds by producing a burst of glass break audio.
If the detector receives the flex and audio signals properly,
its red ALARM LED lights for 3 sec.
If the red ALARM LED does not light, return to
Section 3 RFSS Mode (RF Signal Strength), page 8 to
reposition the detector.
Carefully open the service door of the detector.
Insert a screwdriver into the slot next to the sensitivity DIP
switches (Item 5, Figure 5.19, Page 50).
Touch both test pads at the same time with the tip of the
screwdriver.
When the detector exits from the Test Mode, the green
EVENT LED (Item 6, Figure 5.19, Page 50) stops flashing. If
the EVENT LED continues to flash, repeat Steps 2 and 3.
Stand within 3 m (10 ft) of the detector.
Move the switches on top of the 13-332 Tester to the
ACTIVATE and MAN positions (Items 1 and 3, Figure 5.21,
Page 53).
Point the front of the tester toward the detector and press
the red Start button on top (Item 2, Figure 5.21, Page 53).
The tester buzzes.
System Reference Guide
Bosch Security Systems, Inc.
wLSN